Product: | Elvis |
Version: | 2.x |
Booth: | 2006-08-04 |
Summary
In the properties of the server remote control, the KNX/EIB connection status tab shows “Class not registered” or “RPC server not available”.
Details
The reason may be an incorrect parameterization of the interface under data point connections in the configuration.
The “Computer Name” column and also the “Computer” parameter should normally be left blank unless the bus is not connected to the computer running the Elvis server.
If, for example, a USB interface is used, it is sufficient to specify the name of the connection in the Parameters column. All other entries in the cell must be removed.
e.g.: Connection=USB